Chang, S. H.

Paper Title Page
WPAE001 Helium Distribution for the Superconducting Devices in NSRRC 758
 
  • F.-Z. Hsiao, S. H. Chang, W. S. Chiou, H.C. Li
    NSRRC, Hsinchu
 
  In NSRRC up to five superconducting magnets and one superconducting cavity will be installed in the storage ring. At current stage two superconducting magnets and one superconducting cavity are kept in cold condition by one 450W helium cryogenic system. The crucial stable cryogenic condition required from the superconducting cavity is hard to achieve due to the join of superconducting magnets. A second cryogenic system dedicated for the superconducting magnets is planned in the next stage. A switch valve box serves the function for the backup of two cryogenic systems for each other and a 100 meter nitrogen-shielding helium transfer line dedicated for the five superconducting magnets are installed at end of the year 2004. This paper presents the helium distribution design of the two cryogenic systems and the commission result of the recent work.  
WPAE003 The Cryogenic Supervision System in NSRRC 844
 
  • H.C. Li, S. H. Chang, W. S. Chiou, F.-Z. Hsiao, Z.-D. Tsai
    NSRRC, Hsinchu
 
  The helium cryogenic system in NSRRC is a fully automatic PLC system using the Siemens SIMATIC 300 controller. Modularization in both hardware and software makes it easy in the program reading, the system modification and the problem debug. Based on the Laview program we had developed a supervision system taking advantage of the Internet technology to get system’s real-time information in any place. The functions of this supervision system include the real-time data accessing with more than 300 digital/analog signals, the data restore, the history trend display, and the human machine interface. The data is accessed via a Profibus line connecting the PLC system and the supervision system with a maximum baud rate 1.5 Mbit/s. Due to this supervision system, it is easy to master the status of the cryogenic system within a short time and diagnose the problem.