Author: Cao, G.
Paper Title Page
FROAMA02 A High Heat Load Double Crystal Monochromator and Its Cryo Cooling System for Heps 430
 
  • H. Liang, L. Gao, Y.C. Jiang, W.F. Sheng, S. Tang, A.Y. Zhou
    IHEP, Beijing, People's Republic of China
  • G. Cao
    University of Chinese Academy of Sciences, Beijing, People's Republic of China
 
  A high heat load double crystal monochromator and its cryo cooling system were designed and their prototypes were fabricated for the future HEPS. The mechanical and cooling structure of the DCM are introduced. The FEA results show the DCM is capable of cooling 870 watts of heat load. The cryo cooling system is also introduced. Test results show the pressure stability of the cryo cooling system is less than 2 mbar RMS. Offline heat load test of the DCM were carried out by a ceramic heater attached to the center of the incident surface of the first crystal, and 834 watts heat load were applied by the heater without boiling the liquid nitrogen. Offline absolute vibration measurement of the second crystal assembly was carried out by a laser interferometer under different cryo pump speed, pressure and heat load conditions, to find out the stability performance accordingly. An absolute vibration of 41 nrad RMS was measured, with the pump running at 45Hz, which has a cooling capability of 400 watts.  
slides icon Slides FROAMA02 [7.370 MB]  
DOI • reference for this paper ※ https://doi.org/10.18429/JACoW-MEDSI2018-FROAMA02  