THPMA032 Active Filter for Harmonic Mitigation for Magnet Power Supplies of INDUS-II 671
 
  • Y. P. Singh, S. Kotaiah, A. C. Thakurta
    RRCAT, Indore (M. P.)
 
  Power supplies used for powering of magnets in INDUS-I and INDUS-II uses different type of power converters including SMPS and thyristorised power converters. Though considerations are given to keep the harmonic loading on a.c. mains low while designing these power supplies and selecting a suitable power converter for the required power, still they give a significant amount of harmonic loading on a.c. mains. In all the high power d.c. power supplies, wide variation in operating point leads to a considerable amount of reactive power generation and harmonic loading on ac mains. In this work a study has been performed to know the variation of reactive power with time on some of the d.c. power supplies of INDUS-II. Various options to improve the power factor has been studied and their advantages & limitations for accelerator magnet power supplies has been highlighted. A combined system of a shunt passive and small rated series active filter has been proposed. The compensation principle is described and filtering characteristics are discussed in detail. A scale down prototype of proposed series active filter has been developed in lab and experimental results produced.