Paper | Title | Page |
---|---|---|
TUPEA073 | Status of a Precise Temperature-Regulation System for the C-band Accelerator at XFEL/SPring-8 | 1488 |
|
||
This paper describes the present status of a precise temperature-regulation system for the C-band accelerator at XFEL (X-ray Free Electron Laser)/SPring-8. It is essential to maintain a constant temperature of an rf cavity for stable lasing. We therefore installed a heater-assembly unit into a cooling water circuit of each rf cavity. By controlling the heater power, the temperature of the cavity can be stabilized. We constructed a prototype of this system at the SCSS (SPring-8 Compact SASE Source) test accelerator to check its feasibility for the XFEL. The prototype significantly contributes to a stable supply of SASE to users. For the XFEL, we simplified this system in consideration of cost and controllability. For example, to make one regulation system simultaneously controlling two C-band accelerating structures was tried. Keeping a temperature variation as tight as ±0.02 K at any operational mode could be achieved by this system. The preliminary test results of the system are also reported in this paper. |