TUPPC038 Simultaneous On-line Ultrasonic Flowmetery and Binary Gas Mixture Analysis for the ATLAS Silicon Tracker Cooling Control System 642
 
  • M. Doubek, V. Vacek, M. Vitek
    Czech Technical University in Prague, Faculty of Mechanical Engineering, Prague, Czech Republic
  • R.L. Bates, A. Bitadze
    University of Glasgow, Glasgow, Scotland, United Kingdom
  • M. Battistin, S. Berry, J. Berthoud, P. Bonneau, J. Botelho-Direito, G. Bozza, O. Crespo-Lopez, E. Da Riva, B. Di Girolamo, G. Favre, J. Godlewski, D. Lombard, L. Zwalinski
    CERN, Geneva, Switzerland
  • N. Bousson, G.D. Hallewell, M. Mathieu, A. Rozanov
    CPPM, Marseille, France
  • G. Boyd
    University of Oklahoma, Norman, Oklahoma, USA
  • C. Degeorge
    Indiana University, Bloomington, Indiana, USA
  • C. Deterre
    DESY, Hamburg, Germany
  • S. Katunin
    PNPI, Gatchina, Leningrad District, Russia
  • S. McMahon
    STFC/RAL, Chilton, Didcot, Oxon, United Kingdom
  • K. Nagai
    University of Tsukuba, Graduate School of Pure and Applied Sciences,, Tsukuba, Ibaraki, Japan
  • C. Rossi
    Università degli Studi di Genova, Genova, Italy
 
  We describe a combined ultrasonic instrument for continuous gas flow measurement and simultaneous real-time binary gas mixture analysis. The analysis algorithm compares real time measurements with a stored data base of sound velocity vs. gas composition. The instrument was developed for the ATLAS silicon tracker evaporative cooling system where C3F8 refrigerant may be replaced by a blend with 25% C2F6, allowing a lower evaporation temperature as the LHC luminosity increases. The instrument has been developed in two geometries. A version with an axial sound path has demonstrated a 1 % Full Scale precision for flows up to 230 l/min. A resolution of 0.3% is seen in C3F8/C2F6 molar mixtures, and a sensitivity of better than 0.005% to traces of C3F8 in nitrogen, during a 1 year continuous study in a system with sequenced multi-stream sampling. A high flow version has demonstrated a resolution of 1.9 % Full Scale for flows up to 7500 l/min. The instrument can provide rapid feedback in control systems operating with refrigerants or binary gas mixtures in detector applications. Other uses include anesthesia, analysis of hydrocarbons and vapor mixtures for semiconductor manufacture.