A   B   C   D   E   F   G   H   I   J   K   L   M   N   O   P   R   S   T   U   V   W   X   Y   Z  

Tiessen, H.

Paper Title Page
TUPSM093 New Electron Beam Diagnostics in the FLASH Dump Line 420
 
  • N. Baboi, O. Hensler, D. Lipka, Re. Neumann, M. Schmitz, P.A. Smirnov, H. Tiessen, K. Wittenburg
    DESY, Hamburg
  • A. Ignatenko
    DESY Zeuthen, Zeuthen
 
 

Additional beam diagnostics has been installed in the dump line at FLASH in 2009. Its purpose is to prevent damage by long high current electron beam pulses, as happened in autumn 2008, when a vacuum leak occurred near the dump vacuum window. Beam position monitors (BPM), scintillator-based loss monitors and temperature sensors have been installed thus far in the dump area. Additional BPMs and loss monitors have meanwhile been installed. These include a magnetic BPM placed after the vacuum window. Magnetic loops are used in order to prevent the influence of the ions on the pick-up signals. Four ionization chambers, consisting of air-filled tubes, and 4 glass fibers have been installed parallel to the vacuum pipe, along the last 2 m of beam pipe. Beam halo monitors were installed next to the magnetic BPM. These consist of 4 diamond and 4 sapphire sensors operating as solid state ionization chambers. The halo monitors are sensitive to very small losses. These additional diagnostic monitors were commissioned in autumn 2009, and have contributed to the successful run of long pulses with 3-9 mA current and up to 800 microsecond length. Their performance will be summarized in this paper.